Ampacity Charts - Cerrowire
Maybe your like
In This Section
FIND MY REP Find RetailersWire Size & Amp Ratings
| Copper | Aluminum | ||||
|---|---|---|---|---|---|
| Wire Gauge Size | 60°C (140°F) NM-B, UF-B | 75°C (167°F) THW, THWN, SE, USE, XHHW | 90°C (194°F) THWN-2, THHN, XHHW-2, USE-2 | 75°C (167°F) THW, THWN, SE, USE, XHHW | 90°C (194°F) XHHW-2, THHN, THWN-2 |
| 14 | 15 | 20 | 25 | --- | --- |
| 12 | 20 | 25 | 30 | 20 | 25 |
| 10 | 30 | 35 | 40 | 30 | 35 |
| 8 | 40 | 50 | 55 | 40 | 45 |
| 6 | 55 | 65 | 75 | 50 | 55 |
| 4 | 70 | 85 | 95 | 65 | 75 |
| 3 | 85 | 100 | 115 | 75 | 85 |
| 2 | 95 | 115 | 130 | 90 | 100 |
| 1 | --- | 130 | 145 | 100 | 115 |
| 1/0 | --- | 150 | 170 | 120 | 135 |
| 2/0 | --- | 175 | 195 | 135 | 150 |
| 3/0 | --- | 200 | 225 | 155 | 175 |
| 4/0 | --- | 230 | 260 | 180 | 205 |
| 250 | --- | 255 | 290 | 205 | 230 |
| 300 | --- | 285 | 320 | 230 | 260 |
| 350 | --- | 310 | 350 | 250 | 280 |
| 500 | --- | 380 | 430 | 310 | 350 |
| 600 | --- | 420 | 475 | 340 | 385 |
| 750 | --- | 475 | 535 | 385 | 435 |
| 1000 | --- | 545 | 615 | 445 | 500 |
- Understanding Ampacity: Ampacity refers to the maximum safe current a conductor can carry continuously under specific operating conditions without exceeding its designated temperature limit. Current is measured in amperes (amps). Selecting the appropriate wire size for a circuit is crucial to prevent overheating, which can lead to damage and fire hazards.
- Devices and Amp Draw: The number and type of electrical devices connected to a circuit determine the ampacity requirement of the conductor. For example, a typical general-purpose household circuit is designed for a maximum current of 20 amps, while lighting circuits may be limited to 15 amps.
- Calculating Ampacity Needs: To calculate the load requirement for a circuit, first add up the wattages of all devices planned for the circuit. Divide the total wattage by the system voltage (typically 120V or 240V). This calculation gives you the required current (amps). You may also need to consider voltage drop or derating requirements before making a final determination of the proper conductor size.
WARNING! Installation of electrical wire can be hazardous and, if done improperly can result in personal injury or property damage. For safe wiring practices, consult the National Electrical Code®, your local building inspector, or a qualified electrician.
Ampacities are based on the 2017 NEC and do not reflect any temperature correction or ampacity adjustments that may be required. Please consult a qualified electrician or professional engineer to determine the appropriate values for your specific application.
Tag » What Size Wire For 60 Amp
-
Wire Size For 60 Amp Breaker: Which AWG Wire To Use? (NEC ...
-
What Size Wire For A 60 Amp Breaker? - A Simple Explanation
-
What Size Wire For 60 Amps? Full Guide
-
20, 30, 40, 50, 60 Amp Wire & Breaker Chart: What Size Do I Need
-
60 Amp Wire Size - How To Calculate Proper Wire Gauge
-
What Size Wire Do I Need For 60 Amps? - PortablePowerGuides
-
To Run A 60 Amp Wire 50-60 Feet From A Main Panel, What Gauge Wire ...
-
Wire Size For 60 Amp 220V Circuit - Conquerall Electrical Ltd
-
How To Wire A 60-Amp Breaker: (Explained With Video Guide)
-
60 Amp Wire Size: Everything There Is To Know! - Home Arise
-
What Size Wire Is Needed For 60-Amp Breaker? (Find Out Now!)
-
How To Wire A 2-Pole 60-Amp Breaker | Hunker
-
What Size Wire Should I Use For A 60amp Subpanel?