Two-Stage Surge Current Arrester For Signal Lines

Two-Stage Surge Current Arrester for Signal Lines
KM-DMG-024/1-RB
Surge ProtectionTwo-Stage Surge Current Arrester for Signal Lines SKU: KM-DMG-024/1 RB Category: Surge Protection Tags: Charging Stations, Low Voltage Telephone & Data Lines Protection

Nominal Voltage: 24V DC

Maximum Operating Voltage (AC/DC): 25V AC/36V DC

Two-Stage Surge Current Arrester for Signal Lines quantity Request QuoteDownload PDF SKU: KM-DMG-024/1 RB Category: Surge Protection Tags: Charging Stations, Low Voltage Telephone & Data Lines Protection

Product Information:

Coarse and fine surge protection for 2 core signalling networks.

Features:

  • Screwless terminals
  • Coupling impedance (resistance)
  • Use on systems up to 24 volts

Benefits: Coarse and fine surge protection in differential mode (core-core) and common mode (core-PE). Standards: EN 61643-21 (Surge Protection Devices). Application: Install close to equipment for protection of communication interfaces.

More Information:

Where low voltage, data and telecom lines enter and exit the building, they must also be included in the Lightning Protection System. A lightning surge protection device prevents damage to electrical and electronic equipment from transient over-voltage events by blocking or redirecting surge current to the ground instead of passing through the equipment. These include:

  • Electromagnetic shielding
  • Telephone lines
  • Data communication lines
  • Instrumentation, control, signalling lines
  • Coaxial lines for CCTV, TV, & antenna cables
  • Field based electronic equipment also need to be protected.

    Electrical Specification:

    Order numberKM-DM-048/1-RB
    Connection (input - output)screwless terminals - screwless terminals
    Nominal voltageUn24V DC
    Maximum operating voltage (AC/DC)Uc25V AC/36V DC
    Nominal load currentIL0.5A
    C2 Nominal discharge current (8/20μs) per coreIn5kA
    C2 Nominal discharge current (8/20μs) cores-PEItotal10kA
    C2 Voltage protection level mode core-core at lnUp50V
    C2 Voltage protection level mode core-PE at lnUp350V
    C3 Voltage protection level mode core-core at 1kV/μsUp45V
    C3 Voltage protection level mode core-PE at 1kV/μsUp500V
    Response time core-core/coreta1ns
    Response time core-PEta100ns
    Serial resistance per coreR1.6Ω
    Threshold frequency core-coref5MHz
    Cross-section of connected conductors (solid) (min - max)0.08mm² - 4mm²
    Cross-section of connected conductors (stranded) (min - max)0.08mm² - 2.5mm²
    Degree of protectionIP20
    Range of operating temperatures (min - max)-40°C - +70°C
    MountingDIN rail 35mm
    According to standardEN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 / C2, C3
    ETIM ClassEC 001625
    Weight35g (nett), 60g (gross)

    Wiring Diagrams for Two-Stage Surge Current Arrester for Signal Lines:

    Related products

    KM2-20-4+0 SC
    Type 2 Surge Arrester (KM2-20-4+0 SC)
    KM2-20-1+0 SC
    Type 2 Surge Arrester (KM2-20-1+0 SC)
    KM1+2-25-1+1 SC
    Type 1+2 Lightning Current and Surge Arrester (KM1+2-25-1+1 SC)
    KM1+2-12.5-1 SC
    Type 1+2 Lightning Current and Surge Arrester (KM1+2-12.5-1+0 SC)
    Previous
    Surge Current Arrester for Data, Signal and Telecomms (KM-DM-048/1 RB)
    See All Products
    Next
    Two-Stage Surge Current Arrester for RS485 Signal Lines
    Kingsmill Industries uses cookies to optimize your experience on this site and to offer you services and communications tailored to your interests. By continuing to browse our site, you consent to the use of these cookies. Ok

Tag » What Is A Stage Surge