BX8000 | RS232/RS485 Bus Terminal Controller
Power
Bus Coupler supply
Input for power contacts
Power contacts
SSB connection
Joystick switch
LCD display for diagnosis
Serial interface
Labeling area BX8000 | RS232/RS485 Bus Terminal Controller
- 1
The BX8000 Bus Terminal Controller is a stand-alone PLC. One unit consists of the BX8000 Bus Terminal Controller with up to 64 Bus Terminals and a bus end terminal. With the terminal bus extension system, the connection of up to 255 Bus Terminals is possible.
The controller is programmed via the COM1 interface. In addition, the BX8000 has a second COM port, optionally RS232 or RS485. This can be used for connecting serial devices, such as displays. In terms of their equipment and performance, the BX series Bus Terminal Controllers are positioned between the BC series Bus Terminal Controllers and the CX series Embedded PCs. The main features distinguishing BC and BX are the larger memory and the expanded interfaces of the BX. Additionally, two serial interfaces are integrated for programming and for the connection of further serial devices. The device itself comprises an illuminated LC display with two lines of 16 characters each, a joystick switch and a real-time clock. Further peripheral devices, e.g. displays, can be connected via the integrated Beckhoff Smart System Bus (SSB).
The real-time clock enables decentralized applications, for which the day of the week or the time play an important role. The areas of application for this series are similar to that for the BC series, but due to the larger memory the BX can process significantly more complex and larger programs and can manage more data locally.
Controller for stand-alone applications
Like for all other Beckhoff controllers, the TwinCAT automation software is the basis for parameterization and programming. The BX devices are programmed according to the powerful IEC 61131-3 standard in the programming languages IL, FBD, LD, SFC or ST. Users therefore have the familiar TwinCAT tools available, e.g. the PLC programming interface, the System Manager and TwinCAT Scope. Data are exchanged via the serial port (COM1).
The configuration is also carried out using TwinCAT. The fieldbus interface, the SSB bus and the real-time clock can be configured and parameterized via the System Manager. The System Manager can read all connected devices and Bus Terminals. After the parameterization, the configuration is saved on the BX via the serial interface and can be accessed again later.
Product status:
regular delivery (not recommended for new projects)
Product information
- Technical data
- Accessories
- Documentation and downloads
- Beckhoff Information System
- Additional products
- Related products
- PLC data
- Technical data
- Housing data
| PLC data | RS232/RS485 | BX8000 |
|---|---|
| Programming | TwinCAT (via programming interface or fieldbus) |
| Program memory | 256 kbytes |
| Data memory | 256 kbytes |
| Remanent data | 2 kbytes |
| Persistent data | 1 kbyte |
| Runtime system | 1 PLC task |
| PLC cycle time | approx. 1 ms for 1,000 instructions (without I/O cycle, K-bus) |
| Programming languages | IEC 61131-3 (IL, LD, FBD, SFC, ST) |
| Online change | yes |
| Up/down load code | yes/yes |
- PLC data
- Technical data
- Housing data
| Technical data | BX8000 |
|---|---|
| Number of Bus Terminals | 64 (255 with K-bus extension) |
| Max. number of bytes fieldbus | 512 byte input and 512 byte output |
| Max. number of bytes process image | 2048 byte input and 2048 byte output |
| Digital peripheral signals | 2,040 inputs/outputs |
| Analog peripheral signals | 512 inputs/outputs |
| Data transfer rates | 300 baud…115 kbaud |
| Bus interface | – |
| Interfaces | COM1: 1 x RS232, COM2: 1 x RS232 or RS485 |
| SSB | CANopen-based subsidiary bus system for the connection of further peripheral devices |
| Diagnostics LED | 2 x power supply, 2 x K-bus |
| Display | FSTN display with 2 x 16 characters for diagnosis or own texts, illuminated |
| Switch | joystick switch for parameterisation and diagnosis |
| Clock | battery-powered real-time clock for time and date |
| Power supply | 24 V (-15%/+20%) |
| Input current | 140 mA + (total K-bus current)/4, 500 mA max. |
| Starting current | 2.5 x continuous current |
| Current supply K-bus | 1450 mA |
| Power contacts | max. 24 V DC/max. 10 A |
| Electrical isolation | 500 V (power contact/supply voltage) |
| Weight | approx. 250 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL |
- PLC data
- Technical data
- Housing data
| Housing data | BXxxxx |
|---|---|
| Design form | compact terminal housing with signal LEDs |
| Material | polycarbonate |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Side by side mounting by means of | double slot and key connection |
| Marking | labeling of the BZxxxx series |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
| Stripping length | 8…9 mm |
| Current load power contacts | Imax: 10 A |
| Dimensions (W x H x D) | 81 mm x 100 mm x 90 mm (BX8000: 61 mm x 100 mm x 90 mm) |
*s: solid wire; st: stranded wire; f: with ferrule
Loading content ...
Show moreLoading content ...
Show moreLoading content ...
Show moreLoading content ...
Show more© Beckhoff Automation 2026 - Terms of Use
Please choose your country or region and language
The link was copied to the clipboard. You have successfully logged into myBeckhoff.When you click on "Accept", we show the video and adjust the privacy settings; external content from Video is loaded during this process. Please refer here to our Privacy Policy.
AcceptConsent to export control and sanctions compliance terms
In order to continue to use myBeckhoff, you need to agree to the export control and sanctions compliance terms.If you do not agree to these terms, you will automatically be logged out of myBeckhoff.
Decline AcceptTừ khóa » Bx 8000
-
BX8000 - Introduction - Beckhoff Information System - English
-
CNSLINK_EN | BX8000
-
BX8000 | RS232/RS485 Bus Terminal Controller
-
BX8000 | Beckhoff H2RS232/RS485 Bus Terminal Controller
-
[PDF] BX8000 | RS232/RS485 Bus Terminal Controller
-
SGRTV8BX. 8'' ROUND DOWNLIGHT BX SERIES / 8000 LUMENS ...
-
4760010 PT# 8000-01971 Lancet WaveSense 33g Ultra Thin Sterile ...
-
BX8000-0000 - Manufactured By BECKHOFF - Radwell International
-
Penn Wrath 8000 BX Spinning Fishing Reel NEW @ Otto's ... - EBay
-
Beckhoff Bx8000-0000 Bus Terminal Controller - EBay
-
DISPATCH NBR 8000-8999 1000/BX - RSC Sales
-
Box Awning - RESOBOX BX8000 - Retractable / Manual / Motorized
-
Beckhoff BX8000 Manuals - ManualsLib