Manufacturer: Schneider Electric Barcode: 3606480424373 The C60H-DC A9N61539 circuit breaker is used in DC circuits (industrial circuit control systems, transport, renewable energy, etc.).The circuit breaker performs the functions of protecting circuits against short-circuit and overload currents, as well as control and sectioning functions. Product no longer available
Sign In Sign InPassword Forgotten?Don't have account? Create account SearchSearchClose Product added to basketGo to cartContinue shopping Questions Product categories 



- +7 (495) 663-73-29
- Wishlist
- Compare
- Send
VK
WhatsApp
Odnoklassniki
Copy link
- Model: 003.001.400
Manufacturer: Schneider Electric Barcode: 3606480424373 The C60H-DC A9N61539 circuit breaker is used in DC circuits (industrial circuit control systems, transport, renewable energy, etc.).The circuit breaker performs the functions of protecting circuits against short-circuit and overload currents, as well as control and sectioning functions. Product no longer available - Description
- Dimensions
- Nomenclature
- Delivery
Main
| range | Acti 9 |
| product name | Acti 9 C60H-DC |
| product or component type | Miniature circuit-breaker |
| device short name | C60H-DC |
| device application | Distribution |
| poles description | 2P |
| number of protected poles | 2 |
| [In] rated current | 63 A at 25 °C |
| network type | DC |
| trip unit technology | Thermal-magnetic |
| curve code | C |
| breaking capacity | 10 kA Icu at 440 V DC conforming to EN 60947-210 kA Icu at 440 V DC conforming to IEC 60947-26 kA Icu at 500 V DC conforming to EN 60947-26 kA Icu at 500 V DC conforming to IEC 60947-220 kA Icu at 220 V DC conforming to GB 14048.220 kA Icu at 220 V DC conforming to IEC 60947-220 kA Icu at 250 V DC conforming to GB 14048.220 kA Icu at 250 V DC conforming to IEC 60947-2 |
| utilisation category | Category A conforming to EN 60947-2Category A conforming to IEC 60947-2 |
| suitability for isolation | Yes conforming to IEC 60947-2Yes conforming to EN 60947-2 |
Complementary
| network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 500 V DC |
| [Ics] rated service breaking capacity | 15 kA 75 % conforming to EN 60947-2 - 220 V DC15 kA 75 % conforming to IEC 60947-2 - 220 V DC15 kA 75 % conforming to EN 60947-2 - 250 V DC15 kA 75 % conforming to IEC 60947-2 - 250 V DC4.5 kA 75 % conforming to EN 60947-2 - 500 V DC4.5 kA 75 % conforming to IEC 60947-2 - 500 V DC7.5 kA 75 % conforming to EN 60947-2 - 440 V DC7.5 kA 75 % conforming to IEC 60947-2 - 440 V DC |
| [Ui] rated insulation voltage | 500 V DC conforming to IEC 60947-2500 V DC conforming to EN 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN 60947-26 kV conforming to IEC 60947-2 |
| contact position indicator | Yes |
| control type | Toggle |
| local signalling | ON/OFF indication |
| mounting mode | Fixed |
| mounting support | 35 mm symmetrical DIN rail |
| comb busbar and distribution block compatibility | Top or bottom: standard |
| 9 mm pitches | 4 |
| net weight | 0.256 kg |
| colour | White |
| mechanical durability | 20000 cycles |
| electrical durability | 3000 cycles 500 V DC6000 cycles 500 V DC |
| provision for padlocking | Padlockable |
| locking options description | In position O |
| tightening torque | Power circuit: 2.5 N.m top or bottom |
| earth-leakage protection | Without |
Environment
| standards | EN 60947-2IEC 60947-2 |
| pollution degree | 3 conforming to EN 60947-23 conforming to IEC 60947-2 |
| overvoltage category | IV |
| tropicalisation | 2 conforming to IEC 60068-2 |
| operating altitude | 2000 m |
| ambient air temperature for operation | -25…70 °C |
| ambient air temperature for storage | -40…85 °C |
Dimensions for C60H-DC circuit breakers
36>182P1P815.573441681445Nomenclature of C60H-DC circuit breakers
| Operating voltage Ue | 12…250 V DC | 12…250 V DC | |
| Rated voltage Un | 250 V DC | 500 V DC | |
| Number of poles | 1P | 2P | |
| Curves | C | C | |
| Number of modules W = 9 mm | 2 | 4 | |
| Trip current | 20 kA / 110 V DC10 kA / 220 V DC6 kA / 250 V DC | 20 kA / 220 V DC10 kA / 440 V DC6 kA / 500 V DC | |
| Schemes | 12 | 1234 | 1234 |
| Top or bottom power supply with polarity correct | Top power supply | Bottom power supply | |
| Rated current, A | |||
|---|---|---|---|
| 0.5 | A9N61500 | A9N61520 | |
| 1 | A9N61501 | A9N61521 | |
| 2 | A9N61502 | A9N61522 | |
| 3 | A9N61503 | A9N61523 | |
| 4 | A9N61504 | A9N61524 | |
| 5 | A9N61505 | A9N61525 | |
| 6 | A9N61506 | A9N61526 | |
| 10 | A9N61508 | A9N61528 | |
| 13 | A9N61509 | A9N61529 | |
| 15 | A9N61510 | A9N61530 | |
| 16 | A9N61511 | A9N61531 | |
| 20 | A9N61512 | A9N61532 | |
| 25 | A9N61513 | A9N61533 | |
| 30 | A9N61514 | A9N61534 | |
| 32 | A9N61515 | A9N61535 | |
| 40 | A9N61517 | A9N61537 | |
| 50 | A9N61518 | A9N61538 | |
| 63 | A9N61519 | A9N61539 | |
Сайт использует рекомендательные технологии и файлы cookie
Từ khóa » C60h
-
A9N61506 - Miniature Circuit Breaker - C60H - 1 Pole - 6 A - C Curve ...
-
24871 - C60 - Circuit Breaker - C60H - 3P - 63A - C Curve | Schneider ...
-
Miniature Circuit Breaker - C60H - 2 Poles - 10 A - C Curve - One-Elec
-
[PDF] C60H-DC
-
[PDF] Data Bulletin C60H-DC
-
Acti 9Miniature Circuit Breaker, C60H, 1 Pole, 6A, C Curve - Clipsal
-
C60H/C 40-4 25017 | Elementautomater =< 63 A - Onninen AS
-
Multi 9 C60H-DC Series Thermal Magnetic Circuit Breakers | Newark
-
Acti9 C60H-DC MCBs | Schneider Electric | MISUMI Thailand
-
SCHNEIDER - MCB Breaker, Acti9 C60H, 2P, 6A, C Curve
-
[PDF] C60H Miniature Circuit-breakers - Octopart
-
C60H-DC 2P-10A SCHNEIDER ELECTRIC - Circuit Breaker | DIN
-
Schneider Electric C60H-DC Min. Circuit Breaker, MGN61517, C ...