Flat Slab Design ( Thiết Kế Dầm Bẹt, Tiếng Anh ) - 123doc
Có thể bạn quan tâm
Flat slab design ( Thiết kế dầm bẹt, tiếng anh ) Xác định mặt cắt cần kiểm toán. Tính các giá trị nội lực tại mặt cắt. Xác định vị trí trục trung hòa của tiết diện. Tính ứng suất tại điểm xa trục trung hòa nhất và so sánh với ứng suất cho phép.
Trang 1AND DETAILING
OF FLAT SLAB
ESE SOEDARSONO HS
27 FEBRUARY 2002
Trang 3What is a flat slab?
• a reinforced concrete slab supported directly
by concrete columns without the use of beams
Trang 4Flat slab Flat slab with drop panels
Flat slab with column head Flat slab with drop panel and column head
Trang 5Uses of column heads :
• increase shear strength of slab
• reduce the moment in the slab by reducing the clear or effective span
Flat slab with column head
Trang 6Uses of drop panels :
• increase shear strength of slab
• increase negative moment capacity of slab
• stiffen the slab and hence reduce deflection
Trang 8• Flexibility in room layout
• Saving in building height
• Shorter construction time
• Ease of installation of M&E services
• Prefabricated welded mesh
• Buildable score
Trang 9FLEXIBILITY IN ROOM LAYOUT
• allows Architect to introduce partition walls anywhere required
• allows owner to change the size of room layout
• allows choice of omitting false ceiling and finish soffit
of slab with skim coating
Trang 10SAVING IN BUILDING HEIGHT
• Lower storey height will reduce building weight due to lower partitions and cladding to façade
• approx saves 10% in vertical members
• reduce foundation load
Beam-Free
Trang 11SHORTER CONSTRUCTION TIME
flat plate design willfacilitate the use ofbig table formwork toincrease productivity
Trang 12SINGLE SOFFIT LEVEL
Living Roo m
26 0
• Simplified the table formwork needed
Trang 13EASE OF INSTALLATION
OF M&E SERVICES
• all M & E services can be mounted directly on the underside of the slab instead of bending them to avoid the beams
• avoids hacking through beams
Trang 14PRE-FABRICATED WELDED MESH
• Prefabricated in standard sizes
• Minimised installation time
• Better quality control
• Prefabricated in standard sizes
• Minimised installation time
• Better quality control
Trang 15• allows standardized structural members and
prefabricated sections to be integrated into the design for ease of construction
• this process will make the structure more buildable, reduce the number of site workers and increase the productivity at site
• more tendency to achieve a higher Buildable score
Trang 16CONSIDERATIONS
Trang 17WALL AND COLUMN POSITION
• Locate position of wall to maximise the structural stiffness for lateral loads
• Facilitates the rigidity to be located to the centre of building
Typical floor plan of Compass the Elizabeth
Trang 18STRUCTURAL LAYOUT PLAN
• the sizes of vertical and structural structural members can be optimised to keep the volume of concrete for the entire superstructure inclusive of walls and lift cores to be in the region of 0.4 to 0.5 m3 per square metre
• this figure is considered to be economical and
comparable to an optimum design in conventional of beam and slab systems
Trang 20CRACK CONTROL
• advisable to perform crack width calculations based
on spacing of reinforcement as detailed and the moment envelope obtained from structural analysis
• good detailing of reinforcement will
– restrict the crack width to within acceptable tolerances as specified in the codes and
– reduce future maintenance cost of the building
Trang 21FLOOR OPENINGS
• No opening should encroach upon a column head or drop
• Sufficient reinforcement must be provided to take care of stress concentration
Trang 22PUNCHING SHEAR
• always a critical consideration in flat plate design
around the columns
• instead of using thicker section, shear reinforcement
in the form of shear heads, shear studs or stirrup cages may be embedded in the slab to enhance shear capacity at the edges of walls and columns
Trang 23PUNCHING SHEAR
Shear Studs
Shear Studs
Trang 24• alternatively use 2 sets of forms
Trang 25LATERAL STABILITY
• buildings with flat plate design is generally less rigid
• lateral stiffness depends largely on the configuration
of lift core position, layout of walls and columns
• frame action is normally insufficient to resist lateral loads in high rise buildings, it needs to act in tendam with walls and lift cores to achieve the required
stiffness
Trang 26LATERAL STABILITY
MULTIPLE FUNCTION PERIMETER BEAMS
• adds lateral rigidity
• reduce slab deflection
Trang 27METHODOLOGY
Trang 28METHODS OF DESIGN
• the finite element analysis
• the simplified method
• the equivalent frame method
Trang 29FINITE ELEMENT METHOD
• Based upon the division of complicated structures into smaller and simpler pieces (elements) whose behaviour can be formulated.
• E.g of software includes SAFE, ADAPT, etc
• results includes
– moment and shear envelopes – contour of structural deformation
Trang 35SIMPLIFIED METHOD
Table 3.19 may be used provided
• Live load > 1.25 Dead load
• Live load (excluding partitions) > 5KN/m2
• there are at least 3 rows of panels of approximately equal span in direction considered
• lateral stability is independent of slab column
connections
Trang 36SIMPLIFIED METHOD
Table 3.19: BM and SF coefficients for flat slab or 3 or more equal spans
Outer Support Column Wall
Near centre
of 1st span
First interior span
Centre of interior span
Interior span Moment -0.04Fl* 0.086Fl 0.083Fl* -0.063Fl 0.071Fl -0.055Fl
Shear 0.45F 0.4F - 0.6F - 0.5F
Total column moments
0.04Fl - - 0.022Fl - 0.022Fl
* the design moments in the edge panel may have to be adjusted according to 3.7.4.3
F is the total design ultimate load on the strip of slab between adjacent columns considered
(1.4gk + 1.6 qk)
l is the effective span
Trang 37EQUIVALENT FRAME METHOD
• most commonly used method
• the flat slab structure is divided longitudinally and transversely into frames consisting of columns and strips of slabs with :
– stiffness of members based on concrete alone – for vertical loading, full width of the slab is used to evaluate stiffness
– effect of drop panel may be neglected if dimension <
lx/3
Trang 38EQUIVALENT FRAME METHOD
Plan of floor slab Step 1 : define line of support
in X & Y directions
Trang 39EQUIVALENT FRAME METHOD
9 10 10 9.2 0.8
DESIGN STRIP IN PROTOTYPE
9 10 10.6 10.5 0.8
STRAIGHTENED DESIGN STRIP
DESIGN STRIP IN ELEVATION
Step 2 : define design strips in
X & Y directions
Trang 40FLAT SLAB
Trang 41Effective dimension of a head ,
where l ho = actual dimension, l h max = l c + 2(d h -40)
l h (mm) = lesser of l ho or l h max
Trang 43middle strip (ly-lx/2)
middle strip
ly (longer span)
Trang 44ly (longer span)
note : ignore drop if dimension is less than lx/3
Trang 46MOMENT DIVISION - EXAMPLE
6000 6000 6000 6000 6000
5000
Layout of building
7000 5000
A floor slab in a building where stability is provided by shear walls
in one direction (N-S) The slab is without drops and is supported internally and on the external long sides by square columns The imposed loading on the floor is 5 KN/m 2 and an allowance of 2.5KN/m 2 for finishes, etc fcu = 40 KN/m 2 , fy = 460KN/m 2
Trang 47MOMENT DIVISION - EXAMPLE
Trang 48MOMENT DIVISION - EXAMPLE6000
exterior support = 0.25*35 on 2.5m strip = 3.5KNm centre of 1st span = 0.45*200 on 2.5 strip = 36KNm 1st interior support = 0.25*200 on 3m strip = 16.7KNm centre of interior span = 0.45 *369 on 3m strip = 55.4KNm
Trang 49DESIGN FOR BENDING
INTERNAL PANELS
• columns and middle strips should be designed to withstand design moments from analysis
Trang 50DESIGN FOR BENDING
< 0.5 design moment (EFM)
< 0.7 design moment (FEM)Otherwise structural arrangements shall be changed
M t, max = 0.15 b e d 2 fcu
Trang 511 Calculate V eff =kV t at column perimeter (approx equal span)
V t = SF transferred from slab
k = 1.15 for internal column, 1.25 corner columns and edge columns where M acts parallel to free edge and 1.4 for edge columns where M acts at right angle to free edge
2 Determine vmax= V eff /uo d where uo is the length of column perimeter
Check vma < 0.8 f cu or 5 N/mm 2
3 Determine v=(V eff -V/ud) where u is
the length of perimeter A and V is the
column load and check v < vc
4 Repeat step 3 for perimeter B and C
Column perimeter
Perimeter A
Perimeter B
3d 2
3d 4
3d 4
) lx/3
Trang 52(i) use normal span/effective depth ratio if drop width >1/3 span each way; otherwise
(ii) to apply 0.9 modification factor for flat slab, or
where drop panel width < L/3
Trang 53Holes in areas bounded by the column strips may be formed providing :
• greatest dimension < 0.4 span length and
• total positive and negative moments are redistributed between the remaining structure to meet the changed conditions
ly (longer span)
Trang 54Holes in areas common to two column strips may be formed providing :
• that their aggregate their length or width does not exceed one-tenth of the width of the column strip;
• that the reduced sections are capable of resisting with the moments; and
• that the perimeter for calculating the design shear stress is reduced if appropriate
ly (longer span)
Trang 56For all other cases of openings, it should be framed onall sides with beams to carry the loads to the columns.
Trang 57FLAT SLAB
Trang 58spacing as per design
#Main wire - hard drawn ribbed wire with diameter and
spacing as per design
#Cross wire - hard drawn smooth wire as holding wire
H8-800mm c/c for main wire diameter > 10mm
H7-800mm c/c for main wire diameter of 10mm and below
H7-800mm c/c for main wire diameter of 10mm and below
Trang 59F-Mesh 1
Trang 61TensionLap
Trang 62Main Wire
Plan View of Mesh Layout
Trang 63Main Wire Cross Wire
Trang 64Main Wire Cross Wire
Trang 65FOR INTERNAL PANELS
• Reinforcement are arranged in 2 directions parallel to each span; and
• 2/3 of the reinforcement required to resist negative moment in the column strip must be placed in the centre half of the strip
• for slab with drops, the top reinforcement should be placed evenly across the column strip
Từ khóa » Dầm Bẹt Trong Tiếng Anh
-
Dầm Bẹt Anh Làm Thế Nào để Nói - Việt Dịch
-
Hỏi Về Dầm Bẹt - Diễn đàn Của Các Kỹ Sư Kết Cấu Việt Nam
-
Dầm Bẹt??????? - Diễn đàn Của Các Kỹ Sư Kết Cấu Việt Nam
-
Cách Thức Tính Toán Và Thiết Kế Dầm Bẹt - Tư Vấn Kết Cấu, BTCT, Thi ...
-
Chọn Sơ Bộ Kích Thước Dầm Bẹt - KetcauSoft
-
Lựa Chọn Bề Rộng Dầm Bẹt - KetcauSoft
-
Dầm Bẹt, Sàn Chịu Lực - VnExpress Đời Sống
-
Hướng Dẫn Thiết Kế Dầm Bẹt
-
Tài Liệu Khả Năng Chịu Cắt Của Dầm Bẹt Bê Tông Cốt Thép (tt)
-
ADDICTION - ĐẦM BẸT VAI PHỐI BELT - MIXI | Shopee Việt Nam
-
TS. Đào Ngọc Thế Lực - University Of Da Nang
-
Chỉ Dẫn Thiết Kế Sàn Vượt Nhịp Lớn - SlideShare