R-410A Refrigerant
  • In 1987 the Montreal Protocol, an International environmental agreement, established requirements that began the worldwide phase out of ozone-depleting CFCs (chlorofluorocarbons).
  • In 1992 it was amended to establish a schedule for the phase out of HCFCs (hydrochlorofluorocarbons). HCFCs are less damaging to the ozone layer than CFCs, but still contain ozone-destroying chlorine.
  • The Montreal Protocol is carried out in the U.S. through Title VI of the Clean Air Act, which is implemented by EPA.

HCFC-22

  • HCFC-22 (also know as R-22) has been the refrigerant of choice for industrial process chillers for more than four decades.
  • Unfortunately for the environment, releases of R-22, such as those from leaks, contribute to ozone depletion.
  • In addition, R-22 is a greenhouse gas and the manufacture of R-22 results in a by-product (HFC-23) that contributes to global warming.
  • As the manufacture of R-22 is phased out over the coming years as part of the agreement to end production of HCFCs, manufacturers of industrial process chiller systems are offering equipment that uses ozone-friendly refrigerants.
  • As part of the Montreal Protocol, effective January 1, 2010, Advantage and other industrial process chiller manufacturers no longer build equipment using HCFC-22 (R-22) refrigerant.
  • More and more process chilling equipment is being built using HFC-410A (R-410A) since R-22 can no longer be used.

R-410A

  • R-410A is highly efficient nearly azeotropic mixture (gases evaporate at nearly the same temperatures) of two gasses ideally suited for replacing R-22 in scroll compressor packages.
  • R-410A will not damage the ozone.

  • R-410A has a significantly higher vapor pressure than R-22.
  • The condensing pressure of R-410A at standard conditions for water-cooled chillers is about 340 psi and approximately 390 psi for air-cooled chillers.
  • This is slightly higher than high-pressure safety shut-off settings for R-22.
  • This pressure far exceeds the pressure rating of the components previously used on R-22 systems.
  • Link to Pressure vs. Temperature chart for R-410A, R-407C, R-22, R-404A, R-134A refrigerants.
  • Contractors and technicians need to know that R-410A can only be used in equipment designed for R-410A.
  • It cannot be used to retrofit existing R-22 equipment due to significantly higher operating pressures.
  • Furthermore, special service equipment is required, such as a high pressure manifold gauge set, a high-pressure recovery unit, and high pressure recovery tanks.

Common Questions

  • Where can I get R-410A?
  • All authorized refrigerant distributors should have access to 410A.
  • What about the brands of R-410A?
  • Puron and Suva 410A are marketing brands for ASHRAE R-410A. Puron is Carrier Corp’s brand name and Suva 410A is the DuPont brand name. Both have the same chemical composition and can be used interchangeably.
  • Can R-410A be used to retrofit existing R-22 equipment?
  • No. Because of the much higher discharge pressure and cooling capacity, R-410A should only be used in equipment designed for it.
  • Do I need different service tools to work on R-410A systems?
  • Yes. Because of the higher pressure, you should use manifold gauge sets designed for R-410A. In addition, you should use a recovery unit and tanks designed for the higher pressure of R-410A.
  • What type of lubricant should be used with R-410A?
  • Use a high-quality POE (polyolester) specified by the compressor or system OEM.
  • Will R-410A systems have different components than R-22 systems?
  • Yes. Because of the higher pressure for R-410A, most system components have been designed with increase thickness. In addition, expansion valves specifically designed for R-410A capacity should be used.
  • Is R-410A a blended refrigerant?
  • Yes. It is a blend of two refrigerants, HFC-32 and HCF-125 (50/50 vt%), that performs very much like a single-component refrigerant.
  • How should I charge R-410A?
  • For optimum performance, R-410A should be removed from the cylinder as a liquid.
  • Do I need to replace my current industrial process cooling systems that use R-22?
  • No, R-22 is still available for servicing existing equipment. Chemical manufacturers will be able to produce new R-22 in limited quantities until 2020. Recovered and recycled R-22 is available now and beyond 2020.

Advantage Portable Water Chillers Using R-410A

Air-Cooled Units

Cooling Capacity Pump Capacity Model Tons kW HP GPM

Water-Cooled Units

Cooling Capacity Pump Capacity Model Tons kW HP GPM MGD-10W10.637.2226MGD-15W1552.6336

Titan Series Central Water Chillers Using R-410A

Air-Cooled

ModelTonsHPFlowTI-20W20.5548TI-30W30572TI-40W407.596TI-50W507.5120TI-60W6010144TI-80W85.215240TI-100W10015300TI-120WD12020360TI-150WD14720360TI-180WD17820432TI-90W9015270TI-120W127.820360TI-150W15020420TI-180W18025540

Chilling Modules Using R-410A

Air-Cooled

ModelTons

Outdoor Central Chillers Using R-410A

Single-Zone

ModelTonsBTUHPFlowOACS-10D-MZC-2P1035.2324OACS-15D-MZC-2P14.249.9336OACS-20D-MZC-2P19.668.9348OACS-25D-MZC-2P24.686.5572OACS-30D-MZC-2P29102.0572OACS-40D-MZC-2P37.4131.57.596OACS-50D-MZC-2P47.2166.07.5120OACS-60D-MZC-2P61214.57.5144OACS-80D-MZC-2P74.8263.010192OACS-100D-MZC-2P94330.515240OACS-120D-MZC-2P120.4423.320288OACS-150D-MZC-2P146513.425350OACS-190D-MZC-2P188661.130451OACS-210D-MZC-2P204717.430490

Download the PDF document.