Vortex Flow Meter Upstream And Downstream Requirements
Có thể bạn quan tâm
Required Lengths of Straight Runs
Flow altering devices such as elbows, valves, and reducers can affect accuracy. See the diagram below for typical flow meter system installation.


The recommended guidelines are given to enhance accuracy and maximize performance. The distance given here are minimum requirements; double them for desired straight pipe lengths.
- Upstream: allow a minimum straight pipe length at least 10 times the internal diameter of the pipe. For example, with the 50mm pipe, there should be 500mm of straight pipe immediately upstream. The desired upstream straight pipe length is 1000mm.
- Downstream: allow a minimum straight pipe length at least 5 times the internal diameter of the pipe. For example, with the 50mm pipe, there should be 250mm of straight pipe immediately upstream. The desired upstream straight pipe length is 500mm.
Contact Us
Please prove you are human by selecting the heart. Request a QuoteTừ khóa » Vortex Flow Meter Upstream And Downstream Requirements
-
Sizing And Installing Vortex Meters - Control Global
-
[PDF] Quick Start Guide: Rosemount 8800D Series Vortex Flow Meter
-
Vortex Flow Meter Installation Guide - Control And Instrumentation
-
Flow Measurement: Upstream And Downstream Pipe Diameters
-
Basics Of Vortex Flow Meter (With PDF) - What Is Piping
-
Vortex Flow Meter Straight Piping Line Requirements
-
Vortex Flow Meter Straight Pipe Requirement
-
What Is A Vortex Flow Meter? - Omega Engineering
-
Vortex Flowmeters VY Series | Yokogawa Electric Corporation
-
Upstream And Downstream Flow Straight Pipe Requirements ...
-
DigitalYEWFLO Vortex Flowmeter | Yokogawa Electric Corporation
-
[PDF] Swirl Versus Vortex Flowmeter Technology Swirl Flowmeter Challenges ...
-
Working Principle Of Vortex Flow Meter - InstrumentationTools