BS476 Part 7 - Safety Standards For Thermal Insulation Materials
Có thể bạn quan tâm
British Standard BS 476 Part 7 Fire Test
BS 476 refers to the British standard for fire tests on building materials and structures. This test standard is split into two parts: Part 6 and Part 7. Part 7 specifies the test method for measuring the lateral spread of flame along the surface of a test specimen.
How is Part 7 tested?
The setup: A combustion chamber containing a horizontal gas burner tube and two electrical heating elements is placed below a removable steel chimney and cowl (specimen holder). The specimen is placed in a vertical test position adjacent to the radiation panel, within 5 seconds of igniting a pilot flame.
The procedure: The specimen is set on fire by a pilot flame and this flame is extinguished after a minute. The material might start to burn and the test is terminated when the flame front reaches the 825mm reference line, or after 10 minutes has lapsed, whichever is earlier.
The result: During the test, the following measurements are recorded:
- Time at which the flame front crosses each vertical reference line
- Maximum extent of flame spread during the first 1.5 minutes from the start of the test
- Maximum extent of flame spread during the whole test (i.e. 10 minutes or less, where applicable)
- Time (and distance) at which the maximum flame spread reached.
The flame spread at 1.5 minutes and the final flame spread results are compared with the standard class limits as shown in figure below and a classification is assigned.
What does this mean for my project?
Materials that conform to BS476 provides added assurance about the materials contributing to the overall safety of building occupants in the event of a fire.
If Class 1 classification is required, look out for materials that have been tested according to BS 476 Part 7.
If Class 0 classification is required, the material must either:
- Be composed throughout of materials of limited combustibility, or
- Tested to be a Class 1 material (classified if the material passes the Part 7 test) AND passes the Part 6 test where it has a fire propagation index (I) of not more than 12 and sub-index (i1) of not more than 6.
More on safety standards
BS 476 refers to the British standard for fire tests on building materials and structures. Part 7 specifies the test method for measuring the lateral spread of flame along the surface of a test specimen. During the test, the measurements recorded include... Read more
BS 476 refers to the British standard for fire tests on building materials and structures. Part 6 specifies a method of test for providing a comparative measure of a flat material/assembly's contribution to the growth of a fire. It takes into account the combined effect of factors such as... Read more
The FM approval is an approval requirement for insulation material used on the exterior of non-combustible pipes or ducts. This standard uses a full-scale test for pipe and sheet insulation. Tests in this standard are different from the BS 476 standard as... Read more
The NFPA 274 Standard Test Method is a full-scale test that uses large samples to simulate how insulated pipes in a confined vertical configuration may behave during a growing fire situation. It may be a more realistic assessment as it reflects the actual... Read more
< Return to Armacell Know-how
Contact us
Contact us Company* Name* Telephone* E-Mail* Street Zip* City Message* I consent to Armacell directly marketing to me and providing information concerning its products and offers. Don't fill this field!Discover products
GET SOCIAL Copyright © 2015-2024 Armacell - All rights reserved.To use the Armacell Website with the best user experience and all functions, we recommend that you install a newer browser:
Firefox, Chrome, Internet Explorer
Từ khóa » Tiêu Chuẩn Bs 476 Part 7
-
BS 476 Phần 7 Thiết Bị Kiểm Tra Tính Dễ Cháy / Thiết Bị Kiểm Tra Rải Bề ...
-
BS 476 Phần 7 Vật Liệu Xây Dựng Thiết Bị Kiểm Tra Lửa Thiết Bị Kiểm ...
-
BS476 Part 7 // Understanding Safety Standards - Armacell Vietnam
-
BS 476: Part 7: 1997 Method For Classification Of The Surface ...
-
[Hỏi] Tiêu Chuẩn Kiểm Tra Cháy Vật Liệu Xây Dựng BS476 Phần 7?
-
Tiêu Chuẩn BS 476 - Giá Xây Dựng
-
[PDF] Event-Screen-BS-476-Part-7-Class-1-270216.pdf
-
Thảo Luận - Bảo ôn Cách Nhiệt Như Thế Nào Là Tốt?
-
Thử Nghiệm Chống Cháy - .vn
-
TPFLEX Class 0 - Công Ty Cổ Phần TPTECH
-
Bảo ôn Superlon Sợi - Cơ Khí Phú Hưng
-
[PDF] CỘNG HÒA XÃ HỘI CHỦ NGHĨA VIỆT NAM - Độc Lập - Bộ Xây Dựng
-
Dạng Cuộn - Vật Liệu Cách Nhiệt Kaizen